Bay Area Harness
2 Marina Blvd, Suite B200, San Francisco, CA 94123 · support@bayareaharness.com
ELECTRICAL AND MECHANICAL TEST REPORT
TR-4021-SAMPLE
TR-4021-SAMPLE
Power whip, 4-wire, NEMA L15-30R, 10 AWG
Data Center
3-phase power whip (L1, L2, L3, ground). 10 AWG THHN in 3/4 in. liquid-tight flexible conduit, NEMA L15-30R locking receptacle, 15 ft. Circuit ID labels at both ends.
CustomerSample customer
Customer PO—
DrawingBAH-4021 rev C
LotSAMPLE
Quantity tested3 of 3
WorkmanshipIPC/WHMA-A-620 Class 2
Test date2026-10-25
Serials001–003
Results
| Test | Method | Requirement | Measured | Passed | Status |
|---|---|---|---|---|---|
| Conductor continuity | L1, L2, L3, G, end to end, 1.0 s each | ≤ 0.5 Ω per conductor | 0.220–0.282 Ω | 12 / 12 | PASS |
| AC withstand (hipot) | 1.50 kV AC, 1.0 s, conductors to ground | Total leakage ≤ 5 mA, no breakdown | 1.16–1.28 mA total, 0.043–0.054 mA real | 3 / 3 | PASS |
| Polarity and wiring | L1, L2, L3, G to receptacle terminals | Per drawing | Correct | 3 / 3 | PASS |
| Length | Receptacle box to open end | 15 ft ± 2 in | 15 ft 0–1 in | 3 / 3 | PASS |
| Labeling | Circuit ID at both ends | Matches panel schedule | Accept | 3 / 3 | PASS |
| Visual inspection | Conduit fittings, strip lengths, box seal | IPC/WHMA-A-620 Class 2 | Accept | 3 / 3 | PASS |
Per-serial results
| Step | Test | Reading | Timer | Result |
|---|---|---|---|---|
| Serial 595339-1-SAMPLE | ||||
| 1 | Continuity | 0.229 Ω | 1.0 s | PASS |
| 2 | Continuity | 0.220 Ω | 1.0 s | PASS |
| 3 | Continuity | 0.224 Ω | 1.0 s | PASS |
| 4 | Continuity | 0.268 Ω | 1.0 s | PASS |
| 5 | AC withstand | 1.50 kV · 1.159 mA · 0.043 mA | 1.0 s | PASS |
| Serial 595339-2-SAMPLE | ||||
| 1 | Continuity | 0.229 Ω | 1.0 s | PASS |
| 2 | Continuity | 0.220 Ω | 1.0 s | PASS |
| 3 | Continuity | 0.223 Ω | 1.0 s | PASS |
| 4 | Continuity | 0.266 Ω | 1.0 s | PASS |
| 5 | AC withstand | 1.50 kV · 1.270 mA · 0.054 mA | 1.0 s | PASS |
| Serial 595339-3-SAMPLE | ||||
| 1 | Continuity | 0.230 Ω | 1.0 s | PASS |
| 2 | Continuity | 0.220 Ω | 1.0 s | PASS |
| 3 | Continuity | 0.226 Ω | 1.0 s | PASS |
| 4 | Continuity | 0.282 Ω | 1.0 s | PASS |
| 5 | AC withstand | 1.50 kV · 1.276 mA · 0.054 mA | 1.0 s | PASS |
LOT ACCEPTEDAll 3 assemblies met every requirement on drawing BAH-4021 rev C.
Test equipment
| Instrument | Used for | Calibration |
|---|---|---|
| Hipot / continuity analyzer | AC withstand, ground continuity | Current, record on request |
| Stereo microscope | 10–40× visual inspection | Current, record on request |
Tested by
Reviewed by
Date
This is a sample report with illustrative values. Your report lists your drawing, lot, serial numbers, the requirements on your drawing, and the measured results for every assembly. Questions: support@bayareaharness.com