← Tests and sample reportsBay Area Harness
Bay Area Harness
2 Marina Blvd, Suite B200, San Francisco, CA 94123 · support@bayareaharness.com
ELECTRICAL AND MECHANICAL TEST REPORT
TR-4021-SAMPLE

Power whip, 4-wire, NEMA L15-30R, 10 AWG

Data Center

3-phase power whip (L1, L2, L3, ground). 10 AWG THHN in 3/4 in. liquid-tight flexible conduit, NEMA L15-30R locking receptacle, 15 ft. Circuit ID labels at both ends.

CustomerSample customer
Customer PO—
DrawingBAH-4021 rev C
LotSAMPLE
Quantity tested3 of 3
WorkmanshipIPC/WHMA-A-620 Class 2
Test date2026-10-25
Serials001–003

Results

TestMethodRequirementMeasuredPassedStatus
Conductor continuityL1, L2, L3, G, end to end, 1.0 s each≤ 0.5 Ω per conductor0.220–0.282 Ω12 / 12PASS
AC withstand (hipot)1.50 kV AC, 1.0 s, conductors to groundTotal leakage ≤ 5 mA, no breakdown1.16–1.28 mA total, 0.043–0.054 mA real3 / 3PASS
Polarity and wiringL1, L2, L3, G to receptacle terminalsPer drawingCorrect3 / 3PASS
LengthReceptacle box to open end15 ft ± 2 in15 ft 0–1 in3 / 3PASS
LabelingCircuit ID at both endsMatches panel scheduleAccept3 / 3PASS
Visual inspectionConduit fittings, strip lengths, box sealIPC/WHMA-A-620 Class 2Accept3 / 3PASS

Per-serial results

StepTestReadingTimerResult
Serial 595339-1-SAMPLE
1Continuity0.229 Ω1.0 sPASS
2Continuity0.220 Ω1.0 sPASS
3Continuity0.224 Ω1.0 sPASS
4Continuity0.268 Ω1.0 sPASS
5AC withstand1.50 kV · 1.159 mA · 0.043 mA1.0 sPASS
Serial 595339-2-SAMPLE
1Continuity0.229 Ω1.0 sPASS
2Continuity0.220 Ω1.0 sPASS
3Continuity0.223 Ω1.0 sPASS
4Continuity0.266 Ω1.0 sPASS
5AC withstand1.50 kV · 1.270 mA · 0.054 mA1.0 sPASS
Serial 595339-3-SAMPLE
1Continuity0.230 Ω1.0 sPASS
2Continuity0.220 Ω1.0 sPASS
3Continuity0.226 Ω1.0 sPASS
4Continuity0.282 Ω1.0 sPASS
5AC withstand1.50 kV · 1.276 mA · 0.054 mA1.0 sPASS
LOT ACCEPTEDAll 3 assemblies met every requirement on drawing BAH-4021 rev C.

Test equipment

InstrumentUsed forCalibration
Hipot / continuity analyzerAC withstand, ground continuityCurrent, record on request
Stereo microscope10–40× visual inspectionCurrent, record on request
Tested by
Reviewed by
Date